Fluxer M Series 20kVA ~ 160kVA
With extendable capacity up to 160 kVA / 160 kW in each closet and full DSP control technology, Fluxer M Series is the third generation of three phase high frequency modular UPS.
All internal modules (power module, charger module and monitor module) are modularly designed and hot swappable. In addition, they are constructed with small modules, assuring both system compactness and reliability.
Its full isolation design between fragile components and air flue makes the best of combination of reliability, functionality and flexibility. Moreover, this system adopts advanced ”N+X” wireless parallel and redundancy technology, avoiding single point failure, and further strengthening the reliability.
Characteristics
- High frequency online double-conversion with DSP control
- Hot swappable operation for all modules
- Inbuilt integrated PDU system, easy installation and economic initial investment
- Wide input voltage range, 50 Hz / 60 Hz auto sensing frequency
- Support two modes of frequency conversion: 50 Hz input / 60 Hz output and 60 Hz input / 50 Hz output
- Input power factor > 0.99, input THDi ≤ 3%, output THDV ≤ 5%
- Advanced “N+X” wireless parallel and redundancy technology easily set up different numbers of redundancy UPS module via LCD
- Inbuilt battery module available, 40 × 12 V / 9 Ah for each module
- Share battery pack in parallel operation, saving user’s battery cost
- System capacity up to 160 kVA / 160 kW constructed by each module 20 kVA / 20 kW, single charger module be equipped with 30 A charging current, 4 modules be configured maximally
- Flexible charger parameter and battery configuration setting, selectable battery number: 32 pcs / 34 pcs / 36pcs / 38 pcs / 40 pcs
- Advanced intelligent battery management technique, prolong the working life of battery effectively
- Support battery cold start and mains auto restart
- Complete isolation between key components and air duct effectively improve the system reliability
- Fragile components can be replaced easily as modules at low maintenance cost
- Front accessible maintenance, top / bottom cable entry compatible
- Perfect protection for hardware and software (C class lighting protection, circuit breaker, fuse, software and hardware protection), robust self detection, abundant event log for future check
- 5.7 inches LCD touch screen, friendly human machine interaction
- Standard emergency power off (EPO)
- Standard RS232/USB/RS485/dry contacts communication port
- Optional SNMP communication port
- Optional battery temperature compensation
Technical Specifications
MODEL |
FLUM080T5T0 |
FLUM160T5T0 |
|
Capacity |
80 kVA / 80 kW |
160 kVA / 160 kW |
|
Numbers of parallel module |
1 ~ 4 |
1 ~ 8 |
|
Numbers of redundancy module |
0 ~ 3 |
0 ~ 7 |
|
UPS power module |
20 kVA / 20 kW |
||
INPUT |
|
||
Rated voltage |
380 V / 400 V / 415 Vac |
||
Voltage range |
204 ~ 242 Vac (load ≤ 50%); 242 ~ 277 Vac (50% < load ≤ 70%); 277 ~ 520 Vac (70% < load ≤ 100%) |
||
Rated frequency |
50 / 60 Hz (auto-sense) |
||
Frequency range |
40 ~ 70 Hz |
||
Power factor |
≥ 0.99 |
||
Total harmonic distortion (THDI) |
≤ 3% |
||
Bypass voltage range |
Rated output voltage – 40% ~ rated output voltage + 20% (settable via LCD) |
||
OUTPUT |
|
||
Voltage |
380 V / 400 V / 415 Vac |
||
Voltage regulation |
± 1% |
||
Frequency |
Synchronized with utility in mains mode; 50/60Hz ± 0.1% in battery mode |
||
Power factor |
1.0 |
||
Waveform |
Pure sine wave |
||
Crest factor |
3:1 |
||
Total harmonic distortion (THDV) |
≤ 1% (linear load); ≤ 5% (non-linear load) |
||
Transfer time |
0 ms |
||
Inverter overload capability |
110% ~130%: transfer to bypass in 10 min; 130% ~ 150%: transfer to bypass in 1 min; > 150%: transfer to bypass in 0.5 s |
||
Bypass overload capability |
≤ 150%: long time running > 150%: power off in 10 s |
||
BATTERIES |
|
||
DC voltage |
± 240 Vdc (options: ± 192 Vdc / ± 204 Vdc / ± 216 Vdc / ± 228 Vdc) |
||
Inbuilt battery of standard model |
40 × 12 V / 9 Ah for each module |
||
Charging current |
1 ~ 30 A / 60 A (settable via LCD) |
||
SYSTEM |
|
||
Efficiency |
≥ 94% |
||
Display panel |
5.7 Inches LCD touch screen |
||
Alarm |
Battery mode, low battery, fans fault etc. |
||
EMI |
EN62040-2 |
||
EMS |
IEC61000-4-2 (ESD) |
||
IEC61000-4-3 (RS) |
|||
IEC61000-4-4 (EFT) |
|||
IEC61000-4-5 (Surge) |
|||
COMMUNICAITONS |
|
||
RS232 / RS485 / USB / dry contacts (standard) |
Supports Windows® 98/2000/2003/XP/Vista/2008/7/8/10 |
||
SNMP (option) |
Power management from SNMP manager and web browser |
||
OTHERS |
|
||
Humidity |
0~95% RH @ 0~40℃ (non-condensing) |
||
Noise level |
≤ 60 dB |
||
Module dimensions (W × D × H) (mm) |
482 × 590 × 131 |
||
Module weight |
28 kg / power module, 27 kg / charger module, 7 kg / monitoring module |
||
UPS dimensions (W × D × H) (mm) |
600 × 1000 × 1600 |
600 × 1000 × 2000 |
|
UPS packaged dimensions (W × D × H) (mm) |
700 × 1070 × 1760 |
700 × 1070 × 2160 |
|
UPS Net / Gross weight (kg) Without inbuilt battery and power module |
225 / 245 |
290 / 310 |
|
Input / output / bypass breaker |
Yes |
Yes |