Project Description
Fluxer M Series 50KVA~600KVA
Fluxer M Series is a three phase high frequency on-line double-conversion modular UPS. Its single unit is extendable to 600 KVA, system capacity can be expanded to 2.4 MVA constructed by each power module 50 KVA. All internal modules (Power module, bypass module and control module) are modularly designed and hot-swappable.
Characteristics
- DSP digital control technology
- Pure sine wave double conversion, with strong load capacity
- Flexible modularity and easy scalability with all hot-swappable module design
- Keep high efficiency operation at low load rate: 96% at 40% rated load and 95% at 20% rated load
- High power density of 50 KVA / 3U power module
- 500 KVA system only 1.02 m2 footprint
- Inbuilt integrated PDU system, easy installation and saving investment
- Input power factor > 0.99, THDi < 3%, environment friendly and high-efficiency and energy-saving
- Wide input voltage range, 50 Hz / 60Hz frequency auto-sense, adapt to all kind of grid
- Soft-start technology improves generator matching up to 1:1.1
- Support two modes of frequency conversion: 50 Hz input / 60 Hz output and 60 Hz input / 50 Hz output
- Intelligent hibernation design enable UPS to operate efficiently at low load rate
- Advanced parallel expansion technology, support 4 units in parallel
- Share battery pack in parallel operation, saving user’s battery cost
- Flexible charger parameter and battery configuration setting, battery number 30 ~ 46 pcs selectable
- Intelligent battery management (Intelligent charge/discharge management and float charging voltage temperature compensation), extending battery lifespan
- Support battery cold start and utility self boot
- Self-aging function, easy debugging and test on site
- Fault-tolerant design for fan system: 30% load can be driven when 2 fans fail and 50% load when 1 fan fails
- Front accessible maintenance, top/bottom cable entry compatible
- Complete hardware and software protection function, robust self-diagnostic function, and abundant event log for check
- 7 inches LCD touch screen, friendly human-machine interface
- Monitoring unit with built-in SNMP, supports RS485 and dry contacts
Technical Specifications
MODEL |
FLUM200T5T0 |
FLUM300T5T0 |
FLUM400T5T0 |
FLUM500T5T0 |
FLUM600T5T0 |
FLUM800T5T0 |
|
Rated capacity |
200KVA |
300 KVA |
400KVA |
500KVA |
600KVA |
800KVA |
|
Numbers of power modules |
4 |
6 |
8 |
10 |
12 |
16 |
|
Rated capacity of power module |
50KVA |
||||||
INPUT | |||||||
Input wiring |
3Ph+N+PE |
||||||
Rated voltage |
380/400/415Vac |
||||||
Voltage range |
138 ~ 485 Vac (305 ~ 485 Vac without power downgrading; |
||||||
Input frequency |
40~ 70Hz |
||||||
Power factor |
≥0.99 |
||||||
Current distortion |
<3% |
||||||
BATTERIES | |||||||
Battery voltage |
± 240 Vdc (±180, ± 192, ± 204, ± 216, ± 228, ± 252, ± 264, ± 276 selectable) |
||||||
Number of battery |
40 pcs12 V batteries ( 30 / 32 / 34 / 36 / 38 / 42 / 44 / 46 pcs selectable) |
||||||
OUTPUT | |||||||
Output wiring |
3Ph+N+PE |
||||||
Rated voltage |
380/400/415Vac±1% |
||||||
Frequency |
Synchronized with utility in mains power mode: |
||||||
Power factor |
0.9 |
||||||
Voltage distortion |
≤1% with liner load / ≤3% with non-linear load |
||||||
Crest factor |
3:1 |
||||||
Inverter overload capacity |
105% < load ≤ 110%: transfer to bypass in 60 mins 110% < load ≤ 125%: transfer to bypass in 10 mins 125% < load ≤ 150%: transfer to bypass in 1 min Load > 150%: transfer to bypass in 200 ms |
||||||
Bypass overload capacity |
Load ≤135% for long term; <1000% load for 100 ms |
||||||
SYSTEM | |||||||
Efficiency |
96% |
||||||
Max. number of parallel |
4 units |
||||||
Transfer time |
0ms |
||||||
Protection |
Short circuit protection, overload protection, over-temperature protection, battery low voltage protection, output over/low voltage protection, fans failure protection etc. |
||||||
Communications |
RS485, dry contacts, SNMP |
||||||
Display |
7 inches LCD touch screen |
||||||
OTHERS | |||||||
Operating temperature |
0 ~ 40℃ |
||||||
Storage temperature |
-40℃ ~ 70℃ |
||||||
Humidity |
0 ~ 95%(non-condensing) |
||||||
Altitude |
≤1000m. Above 1000m, derating 1% for each additional 100 m |
||||||
Protection level |
IP20 |
||||||
Noiselevel at 1 m |
<65 dB |
<68 dB |
|||||
Cabinet dimensions (WxDxH) (mm) |
600×850×2000 |
1200×850×2000 |
1400×850×2000 |
2400×850×2000 |
|||
UPS module dimensions (WxDxH) (mm) |
442 ×620 × 130 |
||||||
Cabinetweight (kg) |
233 |
415 |
465 |
617 |
1025 |
||
UPS module weight (kg) |
32 |