Project Description

Fluxer S Series 6~10KVA

Code: FLUS060T2X0, FLUS100T2X0

Fluxer S Series 6~10KVA Power Factor 0.9 is the UPS with advanced DSP digital control technology is applied to rectifier and inverter, having the functions of effective software and hardware protection function, powerful self-diagnostic function.

Characteristics

  • High frequency on-line double conversion technology
  • DSP (Digital signal processors) technology
  • Active power factor correction (APFC), input power factor up to 0.99
  • Output power factor 0.9
  • Wide input voltage range (110V ~ 300Vac) and frequency range (40 ~ 70Hz)
  • Auto sensing frequency
  • 50/60Hz frequency conversion
  • Cold start
  • Rear ventilation design and variable speed fan
  • Effective software and hardware protection
  • Flexible battery configuration (Settable 14 – 20 pcs batteries)
  • Quick and stable charging, 90% capacity restored in 4 h (standard model UPS)
  • Linear derating in low voltage input reducing battery discharging times
  • Settable delayed start when power is restored
  • Advanced battery management (ABM)
  • Multiple functions settable via LCD: output voltage, battery quantity, EOD, EPO, ECO mode, frequency conversion mode and parallel enable
  • Powerful background software for parameters configuration, function settings and online updating
  • Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)

Available Options

  • Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, maintenance bypass, EPO function, parallel function, battery temperature compensation and EMD environmental sensors

Technical Specifications

MODEL FLU S 060 T2x0 FLU S 100 T2x0
Capacity 6 KVA / 5400 W 10 KVA / 9000 W
INPUT
Rated voltage 208 V / 220 V / 230 V / 240 Vac
Voltage range 110 ~ 160 Vac (linear derating between 50% and 100% load);
160 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%)
Rated frequency 50 / 60 Hz (auto-sense)
Frequency range 40 ~ 70 Hz
Power factor ≥ 0.99
Total harmonic distortion (THDI) ≤ 5%
Bypass voltage range – 40% ~ + 15% (settable)
OUTPUT
Voltage 208 V / 220 V / 230 V / 240 Vac (settable)
Voltage regulation ± 1%
Frequency 45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode)
Waveform Pure sine wave
Crest factor 3:01
Total harmonic distortion (THDV) ≤ 2% (linear load); ≤ 5% (non-linear load)
Transfer time Mains mode to battery mode: 0 ms; Inverter mode to bypass mode: 0 ms
Inverter overload capability 102% ~ 125%: Transfer to bypass in 10 mins;
125% ~ 150%: Transfer to bypass in 1 min;
> 150%: Transfer to bypass in 0.5 s
Bypass overload capability 102% ~ 125%: Shut down in 20 mins;
125% ~ 150%: Shut down in 2 mins;
> 150%: Shut down in 1 s
BATTERIES
DC voltage 192 VDC (168/180/192/204/216/228/240VDC optional)
Inbuilt battery 16×7 Ah 16× 9 Ah
Recharge time Standard model (S): 90% capacity restored in 4 hours;
Long time model (H): depend on the capacity of battery
SYSTEM
EFFICIENCY ≥ 93%, ECO mode 98%
Display LCD+LED
Alarms Battery mode, battery voltage low, fans fault etc.
Maximum Parallel numbers 6
EMI IEC/EN62040-2
EMS IEC 61000-4-2 (ESD)
IEC 61000-4-3 (RS)
IEC 61000-4-4 (EFT)
IEC 61000-4-5 (Surge)
COMMUNICATIONS
RS232 / USB / RS485 / dry contacts Supports Windows 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10
SNMP Power management from SNMP manager and web browser
OTHERS
Humidity 20 ~ 90% RH @ 0 ~ 40°C (non-condensing)
Noise level ≤ 55 dB (1m)
Dimensions (W×D×H) (mm) 191×462×710 191×462×710
Packaged dimensions (W*D*H) (mm) 308×640×896 308×640×896
Net weight (kg) 58.7 67.2
Gross weight (kg) 64.8 73.3