Project Description
Fluxer T Series 10~120KVA
Fluxer T Series 10~120KVA online UPS 3-phase in/3-phase out is the high density version of three phase on-line double-conversion UPS designed in small footprints with DSP technology and input power factor correction (PFC), output power factor 0.9, offering high levels of reliability and protection for IT systems, telecommunications equipment and mission critical systems, ensuring maximum power reliability.
Its modularized design of subsystem make easy maintenance on site, and its high overall efficiency ensures low power consumption. Excellent N+1 redundancy parallel design makes 6 units maximum line system possible.
Characteristics
- High frequency online double-conversion with DSP control
- Modular design, high reliability, easily maintenance
- Double input distribution, higher reliability of system
- Input power factor correction (PFC)
- ECO mode operation for energy saving
- Wide input voltage range, 50 Hz / 60 Hz auto-sense frequency
- Support two modes of frequency conversion: 50 Hz input / 60 Hz output and 60 Hz input / 50 Hz output
- Input power factor > 0.99, input THDi ≤ 3%, output THDV ≤ 5%
- Output power factor 0.9
- High efficiency: load > 10%, efficiency ≥ 90%; load > 50%, efficiency ≥ 93%
- Digitized charger: flexible charger parameter and battery configuration setting, monitoring battery disconnected on line
- Share battery pack in parallel operation or separate battery pack for different UPS
- Flexible charger parameter and battery configuration setting, selectable battery number:32 pcs / 34 pcs / 36 pcs / 38 pcs / 40 pcs
- Advanced intelligent battery management technique, prolong the working life of battery effectively
- Support battery cold start and mains supply self-starting
- 5.7 inches LCD touch screen, friendly human & machine interface
- Perfect protective function in hard and software, robust self-diagnosing, abundant event log for future check
- Perfect password control technology, including the first power-on password control, user password control and Maintenance password control
- Reminders of battery out of warranty
- Standard emergency power off (EPO)
- Standard RS232 / USB / RS485 / dry contacts communication port
- Optional SNMP communication port
- Optional N+1 redundancy parallel up to 4 units
- Optional built-in isolation transformer
- Optional battery temperature compensation
Technical Specifications
MODEL |
FLUT010T5T0 |
FLUT020T5T0 |
FLUT030T5T0 |
FLUT040T5T0 |
FLUT060T5T0 |
FLUT080T5T0 |
FLUT100T5T0 |
FLUT120T5T0 |
Capacity |
10 KVA |
20 KVA |
30 KVA |
40 KVA |
60 KVA |
80 KVA |
100 KVA |
120 KVA |
INPUT |
||||||||
Rated voltage |
380 V / 400 V / 415 Vac |
|||||||
Voltage range |
204 ~ 242 Vac (load ≤ 50%); |
|||||||
Rated frequency |
50 / 60 Hz (auto-sense) |
|||||||
Frequency range |
40 ~ 70 Hz |
|||||||
Power factor |
≥ 0.99 |
|||||||
Total harmonic distortion (THDI) |
≤ 3% |
|||||||
Bypass voltage range |
Rated output voltage -40% ~ rated output voltage + 20% (settable via LCD) |
|||||||
OUTPUT |
||||||||
Voltage |
380 V / 400 V / 415 Vac |
|||||||
Voltage regulation |
± 1% |
|||||||
Frequency |
Synchronized with utility in mains mode; |
|||||||
Frequency conversion mode: 50 Hz input and 60 Hz output or 60 Hz input and 50 Hz output |
||||||||
50 / 60 Hz in battery mode |
||||||||
Waveform |
Sinusoidal |
|||||||
Crest factor |
3:1 |
|||||||
Total harmonic distortion (THDV) |
≤ 1% (linear load); ≤ 5% (non-linear load) |
|||||||
Transfer time |
0 ms |
|||||||
Inverter overload capability |
102% ~ 127%: transfer to bypass in 10 mins; |
|||||||
Bypass overload capability |
≤ 150%: long time running |
|||||||
BATTERIES |
||||||||
DC voltage |
± 192 V (options: ± 204 V / ± 216 V / ± 228 V / ± 240 V) |
|||||||
Inbuilt battery of standard model |
32×12 V / 9 Ah |
64×12 V / 9 Ah |
No |
|||||
Charging current |
1 ~ 12 A (settable via LCD) |
1 ~ 24 A (settable via LCD) |
1 ~ 24 A (settable via LCD) |
|||||
SYSTEM |
||||||||
Efficiency |
≥ 93%, ECO mode 98.5% |
|||||||
Display panel |
5.7 Inches LCD touch screen |
|||||||
Alarm |
Battery mode, low battery, fans fault etc |
|||||||
Max. parallel numbers |
4 |
|||||||
EMI |
EN62040-2 |
|||||||
EMS |
IEC61000-4-2 (ESD) |
|||||||
IEC61000-4-3 (RS) |
||||||||
IEC61000-4-4 (EFT) |
||||||||
IEC61000-4-5 (surge) |
||||||||
COMMUNICAITONS |
||||||||
RS232 / RS485 / USB / dry contacts (standard) |
Supports Windows® 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10 |
|||||||
SNMP (optional) |
Power management from SNMP manager and web browser |
|||||||
OTHERS |
||||||||
Humidity |
0 ~ 95% RH @ 0 ~ 40℃ (non-condensing) |
|||||||
Noise level |
≤ 60 dB |
|||||||
Dimensions (W×D×H) (mm) |
600×800×1360 |
600×800×1680 |
||||||
Packaged dimensions (W×D×H) (mm) |
720×920×1500 |
720×920×1820 |
||||||
Net / Gross weight (kg) |
180 / 200 |
186 / 205 |
188 / 210 |
227 / 245 |
231 / 250 |
316 / 376 |
354 / 414 |