Project Description

Fluxer M Series 25KVA ~ 125KVA

Fluxer M Series (25kVA ~ 125kVA) UPS is a high-end modular UPS with latest DSP control technology and most reliable, famous brand components.

It adopts a highly intelligent modular design, which mainly contains power modules, bypass module and control module,all modules support “plug & play” to simplify UPS servicing and maintenance.

The available UPS power and redundancy level can expand vertically from 25 kVA / 25 kW to 125 kVA / 125 KW in one single power cabinet with flexible configuration for meeting different needs.

Based on superior electrical performance, perfect hardware and software protection function, Fluxer M Series UPS can adapt to different grid environment and provides maximum protection and high quality power for critical loads in data centers or other important applications.

Characteristics

  • DSP microprocessor control technology
  • True On-line, double conversion power protection, and with strong load capacity
  • Modular Hot-swappable design for easy maintenance and scalability
  • High efficiency up to 96.5% at most frequently-used load rate
  • Inbuilt integrated PDU system simplifying installation and saving investment
  • Output power factor 1.0, input power factor 0.99, input THDi<3%, output THDv≤ 1%
  • 138 ~ 485 Vac wide input voltage range, 50 Hz / 60 Hz grid self-adaptive
  • Soft-start technology improves generator matching up to 1:1.1
  • Support two modes of frequency conversion: 50 Hz input / 60 Hz output and 60 Hz input / 50 Hz output
  • Intelligent hibernation mode upgrading enables UPS to operate efficiently at low load rate
  • Advanced parallel and redundancy technology, support 4 units connected in parallel
  • Share battery pack in parallel operation, saving user’s battery cost
  • Flexible charger parameter and battery configuration settings, battery number 30 ~ 46 pcs selectable
  • Intelligent battery management technology (Intelligent charge/discharge management and float charging voltage temperature compensation), extending battery lifespan
  • Support cold start with battery and auto restart with mains power
  • Self-aging function to simplify debugging and test on site
  • Fault-tolerant design for fan system, taking 30% loads when 2 fans fail and 50% loads when 1 fan fails
  • Superior hardware and software protection function, robust self-diagnostic function, and abundant event log for check
  • 7 inches LCD touch screen, friendly human-machine interface
  • System with built-in SNMP, supporting RS485 and dry contacts
  • Back-feed protection function (optional)

Technical Specifications

MODEL

FLUM125T5T0

Rated capacity of system cabinet 125kVA
Number of power module 5
Rated capacity of power module 25kVA
INPUT      
Input wiring Three-phase five-wire (3φ+N+PE)
Rated voltage 380Vac/400Vac/415Vac
Voltage range 135 ~ 305Vac (linear derating), 305 ~ 485Vac (no derating)
Frequency range 40~70Hz
Input power factor Full load> 0.99; half load> 0.98
THDi < 3% (linear full load); < 5% (non-linear full load)
Battery voltage ±240VDC (±180, ±192, ±204, ±216, ±228, ±252, ±264, ±276, selectable)
Number of battery 40 pcs 12 V batteries (30, 32, 34, 36, 38, 42, 44, 46 pcs selectable)
OUTPUT
Output wiring Three-phase five-wire (3φ+N+PE)
Rated voltage 380 Vac / 400 Vac / 415 Vac
Output voltage regulation accuracy ±1%
Output frequency accuracy Synchronized with utility in mains power mode; 50 Hz / 60 Hz ± 0.05% in battery mode;
Output power factor 1
Output waveform distortion (THDv) ≤ 1% (linear load);  ≤ 4% (Non-linear load)
Crest factor 3:1
Inverter overload capacity 105% < load ≤ 110%: transfer to bypass in 60 mins 110% < load ≤ 125%: transfer to bypass in 10 mins 125% < load ≤ 150%: transfer to bypass in 1 min Load > 150%: transfer to bypass in 300 ms
Bypass overload capacity Temperature≤30℃, load ≤135% for long term; temperature≤40℃, load ≤125% for long term; load >1000% for 0.1 s
SYSTEM
Efficiency Up to 96%
Max. number of parallels 4
Transfer time 0ms
Protection Lack-phase protection, phase sequence error protection, short circuit protection, overload protection, over-temperature protection, battery low voltage protection, output undervoltage protection, fans failure protection etc.
Communications RS485, dry contacts, SNMP
Display 7 inches LCD touch screen
ENVIRONMENT      
Operating temperature 0℃~ 40℃
Storage temperature –40℃ ~ +70℃
Relative humidity 0% RH ~ 95% RH (non-condensing)
Altitude 0 m ~
≤1000 m, above 1000 m, derating 1% for each additional 100 m
Protection level IP 20
Noise ≤65 dB (at 1 m)
OTHERS
Cabinet dimensions (WxDxH) (mm) 600x850x2000
Module dimensions (WxDxH) (mm) 442x620x86
Cabinet weight (kg) 182.7
Power module weight (kg) 19.1