Project Description

Fluxer S Series 1~3KVA RT

Code: FLUS010RXX0, FLUS020RXX0, FLUS030RXX0

Fluxer S Series 1~3KVA RT online UPS is the high density version of on-line double-conversion UPS with input power factor correction (PFC), output power factor 0.9 offering high levels of reliability and protection for IT systems, telecommunications equipment and mission critical systems.

Characteristics

  • High frequency on-line double conversion technology
  • DSP (Digital signal processors) control technology
  • Active power factor correction (APFC), input power factor up to 0.99
  • Output power factor 0.9
  • Wide input voltage range (110V ~ 300Vac) and frequency range (40 ~ 70Hz)
  • Auto sensing frequency
  • 50/60Hz frequency conversion
  • Cold start
  • Rear ventilation design and variable speed fan
  • Effective software and hardware protection
  • Quick and stable charging, 90% capacity restored in 3 h (standard model UPS)
  • Linear derating in low voltage input reducing battery discharging times
  • Settable delayed start when power is restored
  • Advanced battery management (ABM)
  • Multiple functions settable via LCD: output voltage, EOD, auto-start, bypass mode, ECO mode and frequency conversion mode
  • Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)

Available Options

  • Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, EPO function, MBS (External maintenance bypass switch)

Technical Specifications

MODEL FLU-S 010 R2A0 FLU-S 020 R2A0 FLU-S 030 R2A0
Capacity 1KVA / 900 W 2 KVA / 1800 W 3 KVA / 2700 W
INPUT
Rated voltage 208 V / 220 V / 230 V / 240 Vac
Voltage range 110 ~ 176 Vac (linear derating between 50% and 100% load); 176 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%)
Frequency 40 ~ 70 Hz (auto-sense)
Power factor ≥ 0.99
Bypass voltage -25% ~ +15% (settable)
OUTPUT
Voltage 208 V / 220 V / 230 V / 240 Vac (settable via LCD)
Voltage regulation ± 1%
Frequency 45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode)
Waveform Sinusoidal
Crest factor 3:01
Harmonic distortion ≤ 2% (linear load); ≤ 5% (non-linear load)
Transfer time Mains mode to battery mode: 0 ms
Inverter mode to bypass mode: 4 ms (typical)
Overload capacity 105% ~ 125%: transfer to bypass in 1 min;
125% ~ 150%: transfer to bypass in 30s;
> 150%: transfer to bypass in 300 ms
EFFICIENCY
Mains mode ≥ 90% ≥ 91% ≥ 92%
Battery mode ≥ 85% ≥ 86% ≥ 87%
ECO mode ≥ 95% ≥ 96% ≥ 97%
BATTERIES
DC voltage 24 V 36 V 48 V 72 V 72 V 96 V
Inbuilt battery 2 × 9 Ah 3 × 7 Ah 4 × 9 Ah 6 × 7 Ah 6 × 9 Ah 8 × 7 Ah
Charging current (max.) 1A 1:00 AM 1:00 AM
Recharger time 8 h
ALARMS
Utility failure 4 s per beep
Low battery 1 s per beep
Overload 1 s twice beep
UPS fault Long beep
COMMUNICATIONS
RS232 (standard) / USB (option) Supports Windows®98/2000/2003/XP/Vista/2008/Windows® 7/8 / 10
SNMP (optional) Power management from SNMP manager and web browser
OTHERS
Operating temperature 0~40°C
Relative humidity 0~90%(non-condensing)
Noise level ≤50dB (1m)
Dimensions (W × D × H) (mm) 440 × 468 × 88 440 × 658 × 88 440 × 658 × 88 440 × 468 × 88 (UPS)
440 × 440 × 86 (BAT)
Packaged dimensions (W×D×H) (mm) 545 × 592 × 198 545 × 782 × 198 545 × 782 × 198 545 × 592 × 198 (UPS)
590 × 580 × 200 (BAT)
Net weight(kg) 12.26 13.78 22.73 25.86 29.26 9.45 (UPS)
27.2 (BAT)
Gross weight(kg) 15.78 17.3 26.63 29.76 33.16 12.97(UPS)
30.2 (BAT)

Downloads

Brochure Fluxer Serie S