Project Description
Fluxer T Series 6~20KVA (3:1)
Code: FLUT006T6T0, FLUT010T6T0, FLUT015T6T0, FLUT020T6T0
Besides standard runtime as backup power, Fluxer T Series UPS (long time model)can be fitted with matching battery extension packs for long runtime applications; Besides standard features of normal UPS, it is also able to bear wide input voltage in harsh environment, and support 50/60Hz frequency conversion mode, select input mode via LCD: 3/1 or 1/1; optional N+X redundancy parallel function is also available.Fluxer T Series 6KVA~20KVA online UPS 3-phase in/1-phase out is an on-line double-conversion UPS with output power factor 0.9 offering high levels of reliability and protection for IT systems, telecommunications equipment and mission critical systems, ensuring maximum power reliability.
Characteristics
- High frequency and true double-conversion
- DSP digital control technology
- Wide input voltage range (110 V ~ 300 V)
- Output power factor 0.9
- Optimized battery configuration: 192 V / 240 V
- Cold start
- Auto sensing frequency
- ECO mode operation for energy saving
- 50 / 60 Hz frequency conversion mode
- Selectable output voltage via LCD
- Selectable battery shutdown voltage (EOD) via LCD
- Selectable input mode via LCD ( 3:1 or 1:1)
- Power-on self test
- Advanced battery management (ABM)
- Short circuit and overload protection
- Automatic charging in OFF mode
- Fan speed auto control when temperatures varies
- Standard RS232 / USB communication port
- Standard emergency power off (EPO)
- Optional RS485 / SNMP / AS400 communication port
- Optional extension battery bank
- Optional battery temperature compensation
- Optional built-in isolation transformer
- Optional manual bypass
- Optional N+X redundancy parallel
Technical Specifications
MODEL |
FLUT006T6T0 |
FLUT010T6T0 |
FLUT015T6T0 |
FLUT020T6T0 |
|
Capacity |
6 KVA / 5.4 KW |
10 KVA / 9 KW |
15 KVA / 13.5 KW |
20 KVA / 18 KW |
|
INPUT | |||||
Rated volta |
3:1: 360 V / 380 V / 400V / 415 Vac; |
||||
Voltage range |
3:1: 190 ~277 Vac (derating 50%),277 ~ 520 Vac (no derating); 1:1:110 ~160 Vac (derating 50%),160 ~ 300 Vac (no derating); |
||||
Frequency |
40 ~ 70 Hz (auto-sense) |
||||
Power factor |
3:1: ≥ 0.95; |
||||
BYPASS | |||||
Voltage range |
-40% ~ +15% (settable) |
||||
Frequency |
50 / 60 Hz ± 5 Hz |
||||
OUTPUT | |||||
Voltage |
208 V / 220 V / 230 V / 240 Vac settable via LCD) |
||||
Voltage regulation |
±1% |
||||
Frequency |
Synchronized with utility in mains mode; 50 / 60 ± 0.2 Hz in battery mode |
||||
Waveform |
Sinusoidal |
||||
Crest factor |
3:1 |
||||
Harmonic distortion |
≤ 2%(linear load); ≤ 5% (non-linear load) |
||||
Transfer time |
0 ms |
||||
Overload capability |
105% ~ 125%: transfer to bypass in 3 mins; 125% ~ 150%: transfer to bypass in 30 s; > 150%: transfer to bypass in 0.5 s |
||||
EFFICIENCY | |||||
Mains mode |
≥ 92% |
||||
Battery mode |
≥ 91% |
||||
ECO mode |
≥ 98% |
||||
BATTERIES | |||||
DC voltage |
192 Vdc / 240 Vdc |
||||
Inbuilt battery of standard model |
16 / 20×7 Ah |
16 / 20×9 Ah |
/ |
||
Charging current | Standard model |
1 A |
/ |
||
Long time model |
7A |
||||
Recharge time |
8 h |
||||
ALARM | |||||
Utility failure |
4 s per beep |
||||
Low battery |
1 s per beep |
||||
Overload |
1 s twice beep |
||||
UPS fault |
Long beep |
||||
COMMUNICATIONS | |||||
RS232 / USB (standard) |
Supports Windows® 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10 |
||||
SNMP (optional) |
Power management from SNMP manager and web browser |
||||
OTHERS | |||||
Humidity |
20 ~ 90% RH @ 0~40℃ (non-condensing) |
||||
Noise level |
≤ 58 dB (1m) |
≤ 60 dB (1m) |
|||
Dimensions (W×D×H) (mm) |
262×580×455 (H), 262×580×732 (S) |
262×580×628 (H) |
|||
Packaged dimensions (W×D×H) (mm) |
355×682×615 (H), 359×687×937 (S) |
359×687×832 (H) |
|||
Net weight (kg) |
25.0 (H), 73.0 (S) |
25.5 (H), 74.0 (S) |
38.5 (H) |
39.0 (H) |
|
Gross weight(kg) |
28.5 (H), 82.5 (S) |
29.0 (H), 83.5 (S) |
47.0 (H) |
47.5 (H) |