Project Description

Fluxer S Series 1~3KVA

Code: FLUS010T2X0, FLUS020T2X0, FLUS030T2X0

Fluxer S Series 1KVA~3KVA online UPS is an on-line double-conversion UPS with input power factor correction (PFC), output power factor 0.9 offering high levels of reliability and protection for critical servers and data processing IT systems.

Characteristics

  • High frequency on-line double conversion technology
  • DSP (Digital signal processors) control technology
  • Active power factor correction (APFC), input power factor up to 0.99
  • Output power factor 0.9
  • Wide input voltage range (110V ~ 300Vac) and frequency range (40 ~ 70Hz)
  • Auto sensing frequency
  • 50/60Hz frequency conversion
  • Cold start
  • Rear ventilation design and variable speed fan
  • Effective software and hardware protection
  • Quick and stable charging, 90% capacity restored in 3 h (standard model UPS)
  • Linear derating in low voltage input reducing battery discharging times
  • Settable delayed start when power is restored
  • Advanced battery management (ABM)
  • Multiple functions settable via LCD: output voltage, EOD, auto-start, bypass mode, ECO mode and frequency conversion mode
  • Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)

Available Options

  • Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, EPO function, 12A charger (2-3KVA only) and built-in isolation transformer

Technical Specifications

MODEL FLU S 010 T2x0 FLU S 020 T2x0 FLU S 030 T2x0
Capacity 1 KVA / 900 W 2 KVA / 1800 W 3 KVA / 2700 W
INPUT
Rated voltage 208 V / 220 V / 230 V / 240 Vac
Voltage range 110 ~ 176 Vac (linear derating between 50% and 100% load );
176 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%)
Frequency 40 ~ 70 Hz (auto-sense)
Power factor ≥ 0.99
Bypass voltage range -25% ~ +15% (settable)
OUTPUT
Voltage 208 V / 220 V / 230 V / 240 Vac (settable via LCD)
Voltage regulation ± 1%
Frequency 45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode)
Waveform Sinusoidal
Crest factor 3:01
Harmonic distortion ≤ 2% (linear load); ≤ 5% (non-linear load)
Transfer time Mains mode to battery mode: 0 ms
Inverter mode to bypass mode: 4 ms (typical)
Overload capability 105% ~ 125%: transfer to bypass in 1 min;
125% ~ 150%: transfer to bypass in 30 s;
> 150%: transfer to bypass in 300 ms
EFFICIENCY
Mains mode ≥ 90% ≥ 91% ≥ 92%
Battery mode ≥ 85% ≥ 86% ≥ 87%
ECO mode ≥ 95% ≥ 96% ≥ 97%
BATTERIES
DC voltage 24 V 48 V 72 V
Inbuilt battery 2×9 Ah 4×9 Ah 6×9 Ah
Charging current (max.) 1:00 AM 1:00 AM 1:00 AM
Recharge time 8 h
ALARMS
Utility failure 4 s per beep
Low battery 1 s per beep
Overload 1 s twice beep
UPS fault Long beep
COMMUNICATIONS
RS232 (standard) / USB (optional) Supports Windows® 98 / 2000 / 2003 / XP / Vista / 2008 / Windows® 7 / 8 / 10
SNMP (optional) Power management from SNMP manager and web browser
OTHERS
Operating temperature 0 ~ 40°C
Relative Humidity 0 ~ 90% (non-condensing)
Noise level ≤ 50 dB (1m)
Dimensions (W×D×H) (mm) 44×336×214 191×418×335
Packaged dimensions (W×D×H) (mm) 232×417×318 318×533×471
Net weight (kg) 9.5 18 27.2
Gross weight (kg) 10.5 19.5 29

Downloads

Brochure Fluxer Serie S